23
MAGNUM DIGITAL CONTROLLER (MDC)- LIST OF POSSIBLE ALARMS/DESCRIPTIONS
Shut down and warning fault conditions and the displayed message are described in the following table:
Information
on Binary
Output
Available
1 AnInIOM Sd SD YES
Shutdown alarm configurable on the input of IG-IOM/IGS-PTM.
2 AnInIOM Wrn WRN YES
Warning alarm configurable on the input of IG-IOM/IGS-PTM.
If the controller switches off during starting sequence due to
bad battery condition it doesn't try to start again and activates
this protection.
4 Binary Input Configurable YES
Configurable Warning/Shutdown alarms on the inputs of IL-NT.
5 ChrgAlternFail WRN YES
Failure of the alternator for charging the battery.
If the input
Emergency stop
is opened shutdown is immediately
activated.
7 Engine Temp Sd SD NO
Water temperature is greater than
Sd Water temp
setpoint.
8 Engine Temp Wrn WRN YES
Water temperature is greater than
Wrn Water temp
setpoint.
The generator frequency is out of limits given by
Gen >f
and
Gen <f
setpoints.
10 Fuel Level Sd SD YES
Fuel level is less than
Sd Fuel Level
setpoint.
11 Fuel Level Wrn WRN YES
Fuel level is less than
Wrn Fuel Leve
l setpoint.
12 GCB fail SD NO
Failure of the generator circuit breaker.
13 Igen unbl SD NO
The generator current is unbalanced.
14 Low BackupBatt WRN NO
RTC backup battery is flat.
15 Oil Press Sd SD NO
Oil pressure is less than
Sd Oil press
setpoint.
16 Oil Press Wrn WRN YES
Oil pressure is less than
Wrn Oil press
setpoint.
17 Overload SD YES
The load is greater than the value given by
Overload
setpoint.
The protection comes active if the speed is greater than
Overspeed
setpoint.
Wrong checksum of parameters. Happens typically after
downloading new firmware or changing of the parameter. The
controller stays in INIT mode. Check all parameters write at
least one new parameter.
Failure of the magnetic pick-up sensor for speed measurement.
Shutdown alarm in case of lost connection to IG-IOM/IGS-PTM
module.
22 SprinklActive WRN NO
The protection is active if the output
Sprinkler
is closed.
23 Start failed SD YES
Gen-set start failed
24 Stop fail SD YES
Gen-set stop failed.
Battery voltage is out of limits given by
Batt overvolt
and
Batt
undervolt
setpoints.
During starting of the engine when the RPM reaches the value
of
Starting RPM
setpoint the starter is switched off and the
speed of the engine can drop under
Start RPM
again. Then the
Underspeed protection becomes active. Protection evaluation
starts 5 sec
The generator voltage is out of limits given by
Gen <V
and
Gen >V
setpoints.